*Single ring infiltrometer
*Single ring infiltrometer
*Soil textural classification
*Soil textural classification
+
|}
+
==Safety correction==
+
The measured or calculated infiltration rate must be divided by a value 2 or 3 before use in design<ref>Design criteria for infiltration. (2018, February 14). Minnesota Stormwater Manual, . Retrieved 00:16, March 14, 2018 from https://stormwater.pca.state.mn.us/index.php?title=Design_criteria_for_infiltration&oldid=35583.</ref>
+
{| class="wikitable"
+
|+ Selecting a safety factor
+
|-
+
! 2
+
! 3
+
|-
+
|Catchment < 100 m²
+
|Catchment > 100 m²<ref>Ballard, B. W., Wilson, S., Udale-Clarke, H., Illman, S., Scott, T., Ashley, R., & Kellagher, R. (2015). The SuDS Manual. London.</ref>
+
|-
+
|Permeameter or percolation test on site
+
|Double ring infiltrometer test on site, or grain size analysis used <ref>San Francisco Public Utilities Commission. (2017). Determination of Design Infiltration Rates for the Sizing of Infiltration‐based Green Infrastructure Facilities. Retrieved from http://sfwater.org/modules/showdocument.aspx?documentid=9681</ref>
+
|-
+
|Loamy or sandy soil
+
|Clayey soil<ref>CRC for Water Sensitive Cities. (2015). Adoption Guidelines for Stormwater Biofiltration Systems: Appendix C - Guidelines for filter media in stormwater biofiltration systems.</ref>
|}
|}
Line 44:
Line 61:
*Existing data from borehole, well and geophysical testing; and
*Existing data from borehole, well and geophysical testing; and
*Proposed location of development features (buildings, roads, utilities, etc.).
*Proposed location of development features (buildings, roads, utilities, etc.).
+
===Sampling===
+
+
*The recommendations above are guidelines. Additional tests should be conducted if local conditions indicate significant variability in soil types, geology, water table levels, depth and type of bedrock, topography, etc.
+
*Similarly, uniform site conditions may indicate that fewer test pits are required. Excessive testing and disturbance of the site prior to construction is not recommended. <ref>Christopher B. Burke Engineering LLC. (2009). Soil Infiltration Testing Protocol SOIL INFILTRATION TESTING PROTOCOL Purpose of this Protocol Who Should Conduct Testing. Retrieved from https://www.in.gov/ocra/files/Appendix F - Soil Infiltration Testing Protocol.pdf</re>
−
==Safety correction==
−
The measured or calculated infiltration rate must be divided by a value 2 or 3 before use in design<ref>Design criteria for infiltration. (2018, February 14). Minnesota Stormwater Manual, . Retrieved 00:16, March 14, 2018 from https://stormwater.pca.state.mn.us/index.php?title=Design_criteria_for_infiltration&oldid=35583.</ref>
−
{| class="wikitable"
−
|+ Selecting a safety factor
−
|-
−
! 2
−
! 3
−
|-
−
|Catchment < 100 m²
−
|Catchment > 100 m²<ref>Ballard, B. W., Wilson, S., Udale-Clarke, H., Illman, S., Scott, T., Ashley, R., & Kellagher, R. (2015). The SuDS Manual. London.</ref>
−
|-
−
|Permeameter or percolation test on site
−
|Double ring infiltrometer test on site, or grain size analysis used <ref>San Francisco Public Utilities Commission. (2017). Determination of Design Infiltration Rates for the Sizing of Infiltration‐based Green Infrastructure Facilities. Retrieved from http://sfwater.org/modules/showdocument.aspx?documentid=9681</ref>
−
|-
−
|Loamy or sandy soil
−
|Clayey soil<ref>CRC for Water Sensitive Cities. (2015). Adoption Guidelines for Stormwater Biofiltration Systems: Appendix C - Guidelines for filter media in stormwater biofiltration systems.</ref>
−
|}
----
----