<p>Five percent of the average annual yield (Y<sub>0.05</sub>, in L) is calculated as the product of:
+
<p>Five percent of the average annual yield can be calculated using the following equation:<br>
<ul><li>The catchment area (A, in m<sup>2</sup>)</li>
+
<strong>Y<sub>0.05</sub>= A × C<sub>vol</sub> × R<sub>a</sub> × e × 0.05</strong>
<li>The runoff coefficient for the catchment (C<sub>vol</sub>)</li>
+
<ul>
<li>The average annual rainfall depth (R<sub>a</sub>, in mm)</li>
+
        <li>Y<sub>0.05</sub> = Five percent of the average annual yield (L)
<li> the efficiency of the pre-storage filter (e), and </li>
+
        <li>A = The catchment area ( m<sup>2</sup>)</li>
<li> 0.05 </li></ul></p>
+
        <li>C<sub>vol</sub> = The runoff coefficient for the catchment</li>
<p>Five percent of the average annual demand (D<sub>0.05</sub>) is calculated as the product of:
+
        <li>R<sub>a</sub> = The average annual rainfall depth (mm)</li>
<ul><li> The daily demand per person (P<sub>d</sub>, in L)</li>
+
        <li>e = The efficiency of the pre-storage filter</li>
<li> The number of occupants (n)</li>
+
    </ul>
<li> 365, and </li>
+
</p>
<li> 0.05 </li></ul></p>
+
<p>Five percent of the average annual demand (D<sub>0.05</sub>) is calculated as the product of:<br>
 +
<strong>D<sub>0.05</sub> P<sub>d</sub> × n × 18.25</strong>
 +
<ul>
 +
        <li>D<sub>0.05</sub> = Five percent of the average annual demand (L)</li>
 +
        <li>P<sub>d</sub> = The daily demand per person (L)</li>
 +
        <li>n = The number of occupants</li>
 +
    </ul>
 +
Good catchment selection means that the runoff coefficient (C<sub>vol</sub>) should be 0.9 or greater. Filter efficiency can be reasonably estimated as 0.9 pending manufacturer’s information.</p>
 +
----
 
<p>The following calculation is based upon two criteria:
 
<p>The following calculation is based upon two criteria:
<ol><li>A design rainfall depth is to be captured entirely by the RWH system.</li>
+
    <ol>
<li>The average annual demand (D) is greater than the average annual yield (Y) from the catchment. </li></ol></p>
+
        <li>A design rainfall depth is to be captured entirely by the RWH system.</li>
<p><strong>When Y<sub>0.05</sub>/ D<sub>0.05</sub> <0.33</strong> <br>
+
        <li>The average annual demand (D) is greater than the average annual yield (Y) from the catchment. </li>
The total storage volume required (V<sub>S</sub>, in L) is calculated as the product of:
+
    </ol>
<ul>
+
</p>
<li>The catchment area (A, in m<sup>2</sup>)</li>
+
<p><strong>When Y<sub>0.05</sub>/ D<sub>0.05</sub> <0.33</strong>
<li>The design storm runoff coefficient for the catchment (C<sub>vol</sub>)</li>
+
    <br> The total storage volume required (V<sub>S</sub>, in L) is calculated as the product of:
<li>The design storm rainfall depth (R<sub>d</sub>, in mm), and </li>
+
    <ul>
<li> the efficiency of the pre-storage filter (e). </li></ul>
+
        <li>The catchment area (A, in m<sup>2</sup>)</li>
Good catchment selection means that the runoff coefficient (C<sub>vol</sub>) should be 0.9 or greater.
+
        <li>The design storm runoff coefficient for the catchment (C<sub>vol</sub>)</li>
Filter efficiency can be reasonably estimated as 0.9 pending manufacturer’s information.
+
        <li>The design storm rainfall depth (R<sub>d</sub>, in mm), and </li>
 +
        <li> the efficiency of the pre-storage filter (e). </li>
 +
    </ul>
 +
 
 
</p>
 
</p>
<p><strong>When 0.33 < Y<sub>0.05</sub>/ D<sub>0.05</sub> <0.7</strong> <br>
+
<p><strong>When 0.33 < Y<sub>0.05</sub>/ D<sub>0.05</sub> <0.7</strong>
The total storage required is the sum of V<sub>S</sub> and Y<sub>0.05</sub>. </p>
+
    <br> The total storage required is the sum of V<sub>S</sub> and Y<sub>0.05</sub>. </p>
    