Groundwater

From LID SWM Planning and Design Guide
Revision as of 14:41, 21 February 2018 by Jenny Hill (talk | contribs)
Jump to navigation Jump to search

Where possible, it is recommended that infiltration BMPs maintain a 1.0 m vertical separation above the seasonally high groundwater table.
Retention of this unsaturated zone:

  • Minimizes the potential for functional impacts associated with reduced percolation rates,
  • Maintains the physical and biochemical water quality treatment benefits provided within the vadose zone,
  • Minimizes the potential for localized groundwater mounding to affect nearby buildings or infrastructure, and/or
  • Provides a factor-of-safety against potential uncertainties related to the elevation of the seasonally high groundwater elevation in areas of limited monitoring.

The requirement for additional investigation and/or documentation supporting a proposed design may be reduced in areas where ≥ 1.0 m separation is anticipated.
In areas where a 1.0 m separation cannot be provided, or where conditions dictate that an even greater separation may be warranted, additional discussion and/or analysis specific to the physical characteristics of the site and the proposed design should be completed.
The design practitioner is advised to consult with approval agencies to understand their requirements and/or expectations prior to undertaking work, and to complete an appropriate level of analysis to support their conclusion.

Groundwater mounding[edit]

Groundwater mounding describes the localised raising of the water table beneath infiltration practices. It may be of concern if it affects nearby structures including building foundations.
When you wish to model the extent of groundwater mounding beneath an infiltration facility. This tool uses Hantush's derivation (1967).
Download groundwater mounding calculator(.xlsm)
Note that this is a minor adaptation (metric units and formatting) from the original tool, written and hosted by the USGS.

Reducing groundwater mounding with underdrains[edit]

The yellow box represents the recommended hydraulic conductivity of bioretention filter media

Mounding of groundwater can be mitigated by correctly sizing and spacing of the pipes within the underdrain structure. In most large LID systems, lateral drains should be spaced between 5 - 6 m apart. But when groundwater mounding must be minimized, this distance will be reduced.


This recommendation is supported by an analysis of Hooghoudt's equation [1][2][3] in relation to loamy or clayey native soils, where Kmedia>>Ksoil, finds the first term of the numerator negligible, so that the original equation: may be simplified to:

Where:

  • Kmedia is expressed in m/day
  • Dd is the depth to the drain pipe (m)
  • Dw is the minimum acceptable depth to the water table during infiltration event
  • q is the inflow volume expressed as a depth over the entire surface (m)

  1. H.P.Ritzema, 1994, Subsurface flow to drains. Chapter 8 in: H.P.Ritzema (ed.), Drainage Principles and Applications, Publ. 16, pp. 236-304, International Institute for Land Reclamation and Improvement (ILRI), Wageningen, The Netherlands. ISBN 90-70754-33-9
  2. W.H. van der Molen en J.Wesseling, 1991. A solution in closed form and a series solution to replace the tables for the thickness of the equivalent layer in Hooghoudt's drain spacing equation. Agricultural Water Management 19, pp.1-16
  3. van Beers, W.F.J. 1976, COMPUTING DRAIN SPACINGS: A generalized method with special reference to sensitivity analysis and geo-hydrological investigations, International Institute for Land Reclamation and Improvement (ILRI) Wageningen, The Netherlands