Sizing[edit]

To completely capture linear flow travelling along a gutter perpendicular to a curb inlet, the inlet must be of width::

Where the intention is to capture only a proportion of the flow, the ratio of flow entering the curb inlet may be calculated::

Example[edit]

A curb cut of 3 m is proposed as an inlet for an offline bioretention cell receiving runoff from an adjacent roadway. The gutter and the curb are made from smooth concrete with Manning's 'n' = 0.013. The x-slope is 3% and the longitudinal slope of the road is 2%. The design storm produces flow of 0.08 m3/s.

The width of inlet to capture 100% of this flow is::


Curb cuts Gallery[edit]