!Quantity | !Quantity | ||
|- | |- | ||
− | |'''Pervious | + | |'''Pervious concrete''' |
| | | | ||
* 28 day compressive strength = 5.5 to 20 MPa | * 28 day compressive strength = 5.5 to 20 MPa | ||
Line 13: | Line 13: | ||
|Thickness will range from 100 mm - 150 mm depending on the expected loads | |Thickness will range from 100 mm - 150 mm depending on the expected loads | ||
|- | |- | ||
− | |'''Porous | + | |'''Porous asphalt''' |
| | | | ||
* open-graded asphalt mix with a minimum of 16 % air voids | * open-graded asphalt mix with a minimum of 16 % air voids | ||
Line 19: | Line 19: | ||
|Thickness will range from 50 mm - 100 mm depending on the expected loads | |Thickness will range from 50 mm - 100 mm depending on the expected loads | ||
|- | |- | ||
− | |'''Permeable | + | |'''Permeable pavers''' |
| | | | ||
− | *ASTM No. 8(5 mm dia) | + | *ASTM No. 8(5 mm dia) crushed aggregate is recommended for fill material in the paver openings. |
− | *Pavers shall meet the minimum material and standard specification for | + | *Pavers shall meet the minimum material and standard specification for precast concrete pavers. |
*Pigment in concrete pavers shall conform to ASTM C 979 ACI Report No. 212.3R provides guidance on the use of pigments. | *Pigment in concrete pavers shall conform to ASTM C 979 ACI Report No. 212.3R provides guidance on the use of pigments. | ||
*Maximum allowable breakage of product is 5% | *Maximum allowable breakage of product is 5% | ||
| | | | ||
*For vehicle applications the minimum paver thickness is 80 mm | *For vehicle applications the minimum paver thickness is 80 mm | ||
− | *For pedestrian applications is 60 mm and | + | *For pedestrian applications is 60 mm and joint widths should be no greater than 15 mm. |
|- | |- |
Revision as of 19:37, 19 October 2018
Material | Specification | Quantity |
---|---|---|
Pervious concrete |
|
Thickness will range from 100 mm - 150 mm depending on the expected loads |
Porous asphalt |
|
Thickness will range from 50 mm - 100 mm depending on the expected loads |
Permeable pavers |
|
|