To completely capture linear flow travelling along a gutter perpendicular to a curb inlet, the inlet must be of width::
 
To completely capture linear flow travelling along a gutter perpendicular to a curb inlet, the inlet must be of width::
 
<math>W_T=0.817Q^{0.42}S_{0}^{0.3}\left (\frac{1}{nS_{x}}\right)^{0.6}</math>
 
<math>W_T=0.817Q^{0.42}S_{0}^{0.3}\left (\frac{1}{nS_{x}}\right)^{0.6}</math>
 +
 +
{{Plainlist|1=Where:
 +
*''W<sub>T</sub>'' is the width of the inlet in m,
 +
*''Q'' is the flow perpendicular to the inlet in m<sup>3</sup?/s
 +
*''S<sub>0</sub>'' is the longitudinal slope
 +
*''n'' is Manning's 'n' (between 0.012 and 0.016 for concrete, depending on surface treatment),
 +
*''S<sub>x</sub>'' is the cross slope}}
  
 
Where the intention is to capture only a proportion of the flow, the ratio of flow entering the curb inlet may be calculated::
 
Where the intention is to capture only a proportion of the flow, the ratio of flow entering the curb inlet may be calculated::

Revision as of 19:33, 29 September 2017

Sizing[edit]

To completely capture linear flow travelling along a gutter perpendicular to a curb inlet, the inlet must be of width::

Where:

  • WT is the width of the inlet in m,
  • Q is the flow perpendicular to the inlet in m3</sup?/s
  • S0 is the longitudinal slope
  • n is Manning's 'n' (between 0.012 and 0.016 for concrete, depending on surface treatment),
  • Sx is the cross slope

Where the intention is to capture only a proportion of the flow, the ratio of flow entering the curb inlet may be calculated::

Example[edit]

A curb cut of 3 m is proposed as an inlet for an offline bioretention cell receiving runoff from an adjacent roadway. The gutter and the curb are made from smooth concrete with Manning's 'n' = 0.013. The x-slope is 3% and the longitudinal slope of the road is 2%. The design storm produces flow of 0.08 m3/s.

The width of inlet to capture 100% of this flow is::

The proportion of water entering the bioretention cell under these flow conditions would be::

48% of the 0.08 m3/s flow would enter the bioretenteion cell through the inlet as designed.