Difference between revisions of "Geotextiles"
Jump to navigation
Jump to search
Jenny Hill (talk | contribs) |
Jenny Hill (talk | contribs) |
||
Line 14: | Line 14: | ||
<caption><strong>Recommended criteria for selection of geotextile fabric</strong></caption> | <caption><strong>Recommended criteria for selection of geotextile fabric</strong></caption> | ||
<tr class="success"><th>Percent media passing 0.075 mm (#200 sieve)</th><th>Non-woven fabric apparent opening size (AOS, mm)</th><th>Woven fabric percent open area (POA, %)</th><th>Permittivity (sec<sup>-1</sup>)</th></tr> | <tr class="success"><th>Percent media passing 0.075 mm (#200 sieve)</th><th>Non-woven fabric apparent opening size (AOS, mm)</th><th>Woven fabric percent open area (POA, %)</th><th>Permittivity (sec<sup>-1</sup>)</th></tr> | ||
− | <tr><td align="center" valign="middle">>85</td><td align="center" valign="middle">≤ 0.3</td><td align="center" valign="middle"> | + | <tr><td align="center" valign="middle">>85</td><td align="center" valign="middle">≤ 0.3</td><td align="center" valign="middle">-</td><td align="center" valign="middle">0.1</td></tr> |
<tr><td align="center" valign="middle">50 - 85</td><td align="center" valign="middle">≤ 0.3</td><td align="center" valign="middle">≥ 4</td><td align="center" valign="middle">0.1</td></tr> | <tr><td align="center" valign="middle">50 - 85</td><td align="center" valign="middle">≤ 0.3</td><td align="center" valign="middle">≥ 4</td><td align="center" valign="middle">0.1</td></tr> | ||
<tr><td align="center" valign="middle">15 - 50</td><td align="center" valign="middle">≤ 0.6</td><td align="center" valign="middle">≥ 4</td><td align="center" valign="middle">0.2</td></tr> | <tr><td align="center" valign="middle">15 - 50</td><td align="center" valign="middle">≤ 0.6</td><td align="center" valign="middle">≥ 4</td><td align="center" valign="middle">0.2</td></tr> |
Revision as of 12:36, 5 July 2017
Material specifications should conform to Ontario Provincial Standard Specification (OPSS) 1860 for Class II geotextile fabrics.
- Fabrics should be woven monofilament or non-woven needle punched. Woven slit film and non-woven heat bonded fabrics should not be used as they are prone to clogging.
Primary considerations are:
- Maximum forces that will be exerted on the fabric (i.e., what tensile, tear and puncture strength ratings are required?);
- Load bearing ratio of the underlying native soil (i.e. is the geotextile needed to prevent downward migration of aggregate into the native soil?);
- Texture (i.e., grain size distribution) of the overlying fill material; and
- Permeability of the native soil
- Suitable apparent opening size (AOS) for non-woven fabrics, or percent open area (POA) for woven fabrics, to maintain water flow even with sediment and microbial film build-up;
Percent media passing 0.075 mm (#200 sieve) | Non-woven fabric apparent opening size (AOS, mm) | Woven fabric percent open area (POA, %) | Permittivity (sec-1) |
---|---|---|---|
>85 | ≤ 0.3 | - | 0.1 |
50 - 85 | ≤ 0.3 | ≥ 4 | 0.1 |
15 - 50 | ≤ 0.6 | ≥ 4 | 0.2 |
5 - 15 | ≤ 0.6 | ≥ 4 | 0.5 |
≤ 5 | ≤ 0.6 | ≥ 10 | 0.5 |